UPS model

UPS assets are stored separately from switches and reference encrypted SNMPv3 Monitoring Credential profiles. A UPS can protect multiple switches, with Site-aware assignment rules.

Drivers

ModeDriverProtocolCoverage
autoAuto detectIdentity-first SNMPv3 resolver with vendor MIB enrichment and RFC 1628 fallbackSupported identities below, then Generic UPS-MIB fallback
genericGeneric UPS-MIBIETF RFC 1628 UPS-MIBAny RFC 1628 UPS-MIB device
xppcPhoenixtec / XPPCPhoenixtec XPPC-MIB + RFC 1628Phoenixtec / XPPC-compatible cards and white-label UPS
vertivVertiv / LiebertLiebert Global Products MIB + RFC 1628GXT5, GXE, ITA2, EXM2, EXS, APM2, Trinergy, MTP and Liebert families
socomecSocomec / NET VISION / OFYS-RTSocomec WEB/SNMP + RFC 1628OFYS-RT, NETYS, ITYS, MASTERYS, MODULYS, DELPHYS with WEB/SNMP interfaces
acculineAccuLine TNmaxAccuLine SNMP card + RFC 1628TNmax series with SNMP network card
apcAPC PowerNetAPC PowerNet + RFC 1628Smart-UPS, Easy UPS, Symmetra, Galaxy and PowerNet families
eatonEaton xUPSEaton PowerMIB xUPS + RFC 1628Powerware / Eaton xUPS-compatible families
cyberpowerCyberPower / RMCARDCyberPower RMCARD SNMP + RFC 1628RMCARD-managed Smart App Online, Smart App Sinewave and compatible CyberPower UPS
rielloRiello UPS / NetManRiello NetMan SNMP + RFC 1628NetMan 204 / NetMan 208 managed Riello UPS families

Normalized telemetry

Power drivers normalize standards/vendor evidence into power state, battery state/charge, runtime, load and additional electrical or alarm telemetry where the device reports it. Unsupported objects remain unavailable rather than being converted into false health information.

Incidents and correlation

Portivo can create UPS On Battery, Power Restored, Low Battery and related power incidents. When an offline switch is assigned to a UPS, Portivo can include power evidence and a probable/high-confidence power explanation without presenting an unverified cause as fact.

Temporary transport noise

The monitoring path retains last valid power state across temporary SNMP transport failures and uses confirmation behavior so transient communication noise does not automatically become false power incidents.

Source-backed detail

Polling, details and incident confidence

Regular polling collects a portable core of identity, output source, battery state, charge, runtime, load and alarms when supported. On-demand Details can query a broader vendor surface without increasing background load.

Unsupported objects are omitted rather than rendered as meaningful values. Temporary SNMP failures preserve last-valid telemetry and do not create reachability noise. On-battery and recovery states use confirmation windows before incident history changes.

Correlation boundary

Switch-to-UPS assignments provide context. Portivo reports a probable power cause only when assigned-UPS evidence supports it; simultaneous loss of switch and UPS management connectivity is not proof of hardware failure.